A
Primary return (brine) OUT
B
Primary flow (brine) IN
5.
Connect corrugated pipes to on-
site primary circuit.
6.
Fill primary circuit with Viessmann
"Tyfocor" heat transfer medium
(ethylene glycol/water mixture with
frost protection down to
−
15 °C).
!
Please note
To prevent the brine circuit
pump from being destroyed
(primary circuit pump), never
exceed a glycol concentra-
tion in the heat transfer med-
ium of 30 % (not even for
short periods, i.e. during fill-
ing).
Also, never use the pump for
filling the system (air pock-
ets in conjunction with the
glycol/water mixture can
destroy the pump).
Connections on the primary side of the heat . . .
(cont.)
75
Installation sequence
55
92
968
GB
Installation