The feed for the control unit and the
instantaneous heating water heater is
provided on the main connecting area
X60. The compressor feed comes
from control module X80 (see also
page 54).
The power cables to the main power
circuits must have a suitable cross-
section for the rated current (see spe-
cification from page 195 onwards).
Protect the power cable to the control
unit with a fuse of max. 16 A.
The power fuses for the compressor
must have Z characteristics.
Note
We recommend making the power
connection for accessories and exter-
nal components to the same fuse,
with at least the same phase as the
control unit.
Connection to the same fuse provides
additional safety when the power is
switched off. However, please pay
attention to the power consumption of
the consumers that are connected
when doing this (control unit feed fuse
protection max. 16 A).
Danger
The absence of component earthing can transfer dangerous body cur-
rents, should an electrical fault occur.
The equipment and the pipework must be connected to the earth bonding
of the house in question.
!
Please note
Only for 400 V units:
An incorrect phase sequence can cause damage
to the unit.
The power supply to the compressor
must
have a
clockwise
rotating
field in the phase sequence that is specified at the terminals.
In negotiations with your power sup-
ply utility, different feed tariffs for the
main power circuits may be offered.
The
control unit/electronics
feed
must be implemented
without
possi-
ble blocking from the power supply
utility; tariffs that are subject to possi-
ble shutdowns must not be applied to
these feeds.
The allocation of the power-OFF (for
compressor and/or instantaneous
heating water heater) is made via the
control unit settings (see pages 137
and 142). Blocking of the main supply
is limited to max. 3 times 2 hours per
day (24 h) in Germany.
400 V~ power supply, various tariffs
&
Three separate power cables
&
Selective power-OFF for compressor and instantaneous heating water heater
possible
Power supply
(cont.)
89
Installation sequence
55
92
968
GB
Installation
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...