Compressor power supply
A
Terminals at the control module
Recommended power cable: 3 x 4
mm
2
Note
The upstream fuses must have Z
characteristics.
Instantaneous heating water heater power supply
A
Terminals in the control panel
Max. fuse rating 16 A
Recommended power cable: 7 x 2.5
mm
2
Max. lead length: 30 m
Each heater winding requires its own
neutral conductor.
Never
bridge the
neutral conductor without increasing
the cross-section.
Blue flexible tubing has been provided
with the unit for marking the neutral
conductors in accordance with
VDE 0100, part 430.
Danger
Incomplete phase shutdowns
can lead to the transfer of dan-
gerous body currents, should
an electrical fault occur.
The circuit breakers must be
mechanically
blocked
together. The use of individual
circuit breakers is not accepta-
ble.
Power supply 230 V~, one tariff
&
One common power cable with a large cross-section up to the vicinity of the
heat pump.
&
The common power cable cannot be blocked. Selective blocking of the indivi-
dual power cables must take place downstream of the sub-distribution, which
means additional sub-distribution costs.
Power supply
(cont.)
95
Installation sequence
55
92
968
GB
Installation
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...