Adapt the cross-section of common power cable to the connected load of the
instantaneous heating water heater and the compressor. The connected load of
the control unit does not have to be taken into consideration.
A
Common heat pump power cable
Recommended power cable: 4 x
10 mm
2
B
Control unit, no power-OFF per-
missible
Recommended power cable: 3 x
1.5 mm
2
C
Instantaneous heating water hea-
ter
Recommended power cable: 7 x
2.5 mm
2
D
Compressor
Recommended power cable: 3 x 4
mm
2
E
Sub-distribution (on the heat
pump itself)
Control unit power supply
A
Terminals in the control panel
Note
This supply must
never
be blocked.
Max. protection 16 A.
Power supply
(cont.)
96
Installation sequence
55
92
968
GB