14
Handling by forklift truck or pallet truck
C
C
B
A
A
Select a fork length in line with the
heat pump length, see "Specifica-
tion".
B
The centre of gravity of the
Vitocal 300-G Pro/
Vitocal 300-W Pro (through the heat
exchanger on the l.h. side)
C
Edge protection (e.g. two or three
layers of corrugated cardboard)
Installation
Installation room requirements
!
Please note
The installation room must be dry
and free from the risk of frost.
Safeguard ambient temperatures
of 0 to 35 °C.
!
Please note
Avoid the risk of explosion due to
dust, gases and vapours
in the installation room.
!
Please note
Observe the permissible floor
load.
Total weight, type BW 190 to
BW 2250:
BW 190
720 kg
BW 1120 820 kg
BW 2150 1180 kg
Preparing for installation
Delivery and installation
(cont.)
5772 458 GB