Connections

7

Installation of Tank Temperature Sensor and/or Aquastat

1.

Install reducing coupling (included in
Connection Fitting Package). Use
approved pipe sealant.

2.

Install sensor well using sealant.

Where Vitotronic 200 or 300 is utilized
to control DHW production:

3.

Insert DHW tank temperature sensor
(supplied with Vitotronic 200 or 300)
fully and completely into sensor well.

Due to the length of the stainless steel
well (8.7” / 220 mm), care must be taken
to ensure that the sensing bulb of the
aquastat limit is inserted and pushed to
the end of the stainless steel well.

Where a Vitotronic 100 and a
Viessmann Power/Pump Control Module
are utilized to control DHW production:

3.

Insert the extended capillary of the

aquastat (supplied with Viessmann
Power/Pump Control Module, not
illustrated) fully and completely into
sensor well. Mount aquastat
inconspicuously on tank panelling.
Follow instructions below with regard
to sensor and spring clip installation.

... if aquastat is to be mounted remote
from the aquastat well:

4.

Align sensor bulb with spring clip.

5.

Slide assembly into well.

6.

The retention spring clip must press
the bulb properly to ensure surface
contact with the well.

... if aquastat is to be mounted directly
on the tank well:

7.

Mount aquastat with holding clip
supplied directly onto well. Bend
capillary tube into groove opening to
allow for mounting of aquastat.

5167

514

v1.1

1.

2.

To ensure optimum, safe operation,

the supplied stainless steel well must

be installed. The well diameter is

large enough to accommodate a wide

variety of sensing bulbs.

Always use spring clip to ensure

proper contact of capillary bulb

against the stainless steel well for

proper sensing/heat transfer!

WARNING

IMPORTANT

Summary of Contents for Vitocell 100

Page 1: ... HEAT TRANSFER MEDIUM MUST BE LIMITED TO A MAXIMUM OF 30 PSIG BY AN APPROVED SAFETY OR RELIEF VALVE SEE PAGE 2 CAUTION Read and save these instructions for future reference IMPORTANT Vitocell 100 Installation Instructions Vitocell 100 CHA Series Enameled indirect fired domestic hot water storage tank 42 and 53 USG 160 and 200 ltr capacities 5167 514 v1 1 02 01 Please file in Service Binder ...

Page 2: ...mencing installation Store documentation near boiler in a readily accessible location for reference in the future by service personnel For a listing of applicable literature please see section entitled Important Regulatory and Installation Requirements H Advice to owner Once the installation work is complete the heating contractor must familiarize the system operator ultimate owner with all equipm...

Page 3: ...tion 5 Set up Tank Set up 5 Connections Orientation and Dimensions 6 Installation of Tank Temperature Sensor and or Aquastat 7 Verification of Anode Connection 8 Boiler Water Connections 8 Domestic Hot Water Connections 9 Appendix Pressure Drop Information 11 Post Installation 12 Start up Information 12 Service Binder 12 5167 514 v1 1 ...

Page 4: ...n the equipment The installation adjustment service and maintenance of this equipment must be done by a licensed professional heating contractor who is qualified and experienced in the installation service and maintenance of hot water heating systems There are no user serviceable parts on this equipment Ensure main power supply to equipment the heating system and all external controls has been dea...

Page 5: ...and 200 ltr capacities Enameled indirect fired domestic hot water storage tank with one heat exchanger coil for use with hot water heating boilers Tank Set up H For narrow passageways remove lower portion of crating and carry DHW tank to its final installation site by means of crating boards which are mounted on the tank lengthwise See Installation Instructions of the Transport Handles Accessory t...

Page 6: ...clearances to combustibles Storage capacity USG ltr 42 160 53 200 All sides inches mm 0 0 0 0 Orientation and Dimensions Connections Boiler supply and return DCW DHW and TPV Sensor well for DHW tank temperature sensor aquastat ø ø ø 1 3 4 1 Domestic hot water and TPV Boiler water supply Sensor well for DHW tank temperature sensor aquastat Domestic cold water Boiler water return Consumable anode wi...

Page 7: ...er Pump Control Module not illustrated fully and completely into sensor well Mount aquastat inconspicuously on tank panelling Follow instructions below with regard to sensor and spring clip installation if aquastat is to be mounted remote from the aquastat well 4 Align sensor bulb with spring clip 5 Slide assembly into well 6 The retention spring clip must press the bulb properly to ensure surface...

Page 8: ...sig Max tank testing pressure H heating water side primary 480 psig H DHW side secondary 300 psig 1 Connect heating water side primary connections using supplied adaptors See Installation Instruction Supplement for fittings supplied with tank 2 Control heat supply to the tank according to illustration on the left 3 Pipe supply connections with upward slopes and install an air vent valve at highest...

Page 9: ...red where back flow preventer is installed check local plumbing codes and requirements 1 Connect DHW connections using supplied adaptors See Installation Instruction Supplement supplied with tank 2 Insulate DHW pipe connections Dishwashers and washing machines can be connected to central domestic hot water supply Washing machines must be supplied with a separate domestic cold and hot water connect...

Page 10: ...ect size pressure and temperature relief valve is used and installed is necessary Warranty Our warranty for domestic hot water tanks states that the water heated must be of drinking water quality and that any water treatment equipment in use must function correctly Viessmann accepts no responsibility for damage howsoever caused and reserves the right to withdraw the product warranty if the product...

Page 11: ...80 200 120 300 160 400 200 500 240 600 320 800 1 6 4 2 5 2 4 6 3 2 8 4 10 8 20 12 30 1 2 3 2 2 500 2 6 600 3 5 800 4 4 1 000 9 2 000 13 3 000 18 4 000 22 5 000 26 6 000 35 8 000 5167 514 v1 1 Pressure drop on domestic hot water side secondary circuit Pressure drop Waterflow ltr min USGPM 40 100 w c mbar 1 2 3 1 6 4 2 5 2 4 6 3 2 8 4 10 10 3 8 20 12 30 16 40 20 50 24 60 32 80 167 44 133 35 100 26 8...

Page 12: ...smann us com 12 Post Installation Start up information Start up Service Instructions DHW Tank Service Binder 1 File all Parts Lists Operating and Service Instructions in the Service Binder 2 Install a protective hanging case near the boiler and store the Service Binder in this location For a listing of applicable Viessmann literature please see Important Regulatory and Installation Requirements Te...

Reviews: