8
Installation information
!
Please note
To prevent material losses, install
the combi cylinder in a draught-
free room free from the risk of
frost.
Otherwise the combi cylinder will
have to be drained if there is a risk
of frost and it is not in use.
!
Please note
The thermal insulation must not
be able to come into contact with
naked flames.
Exercise caution when welding
and soldering.
Provide adequate clearance from the
wall so that the thermostat can be oper-
ated (if installed).
Installing the combi cylinder with an
immersion heater
a
Installation instructions, immer-
sion heater
Maintain minimum clearance in front of
the cylinder.
Note
The unheated length of any threaded
immersion heater installed on site must
be at least 100 mm.
Output
Immersion heater
Dimension a
6 kW
min. 650 mm
12 kW
min. 950 mm
Preparing for installation
Product information
(cont.)