16
Fig. 16
1.
Connect the pre-routed lead to the flue gas tem-
perature sensor in the boiler flue connection.
2.
Fill the trap with water, slot it on and tighten.
Condensate drain
■
Connect the trap with the plastic hose to the drain-
age system.
■
Route the condensate drain with a fall and below the
anti-flooding level of the flue gas collector.
■
The condensate drain must be freely accessible for
inspection where it enters the drainage system.
■
External
7
of connection: 17 mm
Danger
Flue gas escaping from the trap can cause
potentially fatal carbon monoxide poisoning.
Always fill the trap with water before commis-
sioning.
Connecting the neutralising system (accessories)
Installation instructions "Neutralising system"
Fitting the trap and flue gas temperature sensor
5839853