Side Wall Vent Installation
a
Fig. 2
Standard side wall venting layout, using basic vent kit components for
vent systems 60/100, 80/125 and 100/150
Max. wall thickness
19.6”/500 mm
12
Side Wall Venting Layouts
Layout with basic coaxial vent kit componentry
Vent pipe adaptor
Elbow,
87° (1 per carton)
Straight pipe
3.3 ft./1 m long
Vent termination
(incl. wall flashings)
Important!
Total length of vent termination pipe is
31”/787 mm. If required, the vent
termination pipe may be shortened by
max. 12”/305 mm (min. vent
termination length is 19”/483 mm
).
Protective screen
Warning!
Protective screen MUST be installed.
Mounting clip,
white (use at least 2)
Brass adaptor
(M8 x
5
/
16
” - 18)
and
Set of screws
(#8 x
3
/
8
”)
(shown on following page)
Combustion air intake
Flue gas outlet
a
Total vent length
*1
*1
See section Vent Length Requirements on
page 21 in this manual.
5
2
8
5
2
6
8
v
3
.8