Direct Venting (Two-pipe System)
41
General Installation Information
Installation steps (outline)
Table 30. Approved materials for two-pipe system
Part
Material
Certified to Standards
Applicability
Exhaust pipe and fitting Stainless steel
UL1738
“Venting systems for
gas-burning appliances,
Categories II, III, IV”
U.S.A.
ULC S636
“Standard for Type BH gas
venting systems”
Canada
CPVC
UL1738
“Venting systems for
gas-burning appliances,
Categories II, III, IV”
U.S.A.
ULC S636
“Standard for Type BH gas
venting systems”
Canada
Combustion air pipe
and fitting
Stainless steel
n.a.
n.a.
and fitting
PVC-DWV
Schedule 40
ANSI/ASTM D2661
CSA B181.1
ULC S102.2
ANSI/ASTM D2665, D1785
CSA B137.3, B181.2
ANSI/ASTM F441
U.S.A./Canada
CPVC
Schedule 40
ANSI/ASTM D2661
CSA B181.1
ULC S102.2
ANSI/ASTM D2665, D1785
CSA B137.3, B181.2
ANSI/ASTM F441
U.S.A./Canada
ABS-DWV
Schedule 40
ANSI/ASTM D2661
CSA B181.1
ULC S102.2
ANSI/ASTM D2665, D1785
CSA B137.3, B181.2
ANSI/ASTM F441
U.S.A./Canada
Pipe cement,
primer (for combustion
air intake pipe)
PVC
ANSI/ASTM D2564
CSA B137.3
U.S.A./Canada
air intake pipe)
CPVC
ANSI/ASTM F493
CSA B137.6
CPVC
ANSI/ASTM F493
CSA B137.6
ABS
ANSI/ASTM D2235
CSA B181.1/B182.1
Pipe cement,
primer (for exhaust
pipe and fitting)
CPVC
ULC S636
“Standard for Type BH gas
venting systems”
Class IIB 90°C
U.S.A./Canada
5
2
8
5
2
6
8
v
3
.8
Do not use cellular (foam) core pipe
material to vent this Vitodens boiler.
CAUTION