Single Wall Venting (Room Air Dependent)
59
General Installation Information
(continued)
Installation steps (outline)
Exhaust vent pipe material
Use only the materials listed in table
41. for exhaust vent pipe fittings.
H
Cut the pipe end square and remove
all burrs and debris from joints and
fittings.
H
If using CPVC special vent material
for exhaust vent pipe, all joints must
be properly cleaned, primed and
cemented. Use only cement and
primer approved for the use with the
pipe material. See table 41. for
approved solvent cement material.
H
No low point is allowed in the
exhaust vent pipe system, unless a
proper drain pipe is used to allow
condensate to drain.
H
Route vent pipe as directly as
possible and with as few bends as
possible to the boiler.
H
Condensate must drain from the flue
pipe to the boiler. Ensure a suitable
gradient of at least 3º (approx. 2” per
3.3 ft. / 50 mm per 1 m).
H
Use a hacksaw and sheet metal snips
to cut pipes to length (if necessary).
Use a file to smooth rough edges.
Pipe must be round and not bent into
an oval shape.
When cutting pipes to length, debur
and clean pipes.
In conjunction with these
instructions, follow the installation
instructions supplied by the special
venting manufacturer.
Viessmann Venting System
Instructions supersede the
instructions supplied by the
manufacturer.
H
All piping must be fully supported.
Use pipe hangers at a minimum of
48” / 1219mm intervals to prevent
sagging of the pipe.
H
The exhaust vent pipe and fittings
must be securely supported by a
support system suitable for the
weight and design of the material
employed. Contact your local vent
material supplier for more information
specific to your installations.
Ensure that the exhaust vent pipes are
properly supported. The Vitodens boiler
is not designed to support the weight
of the exhaust vent pipe system.
H
Field supplied increaser fittings
(transitions) should always be made
in vertical sections of pipe to prevent
accumulation of condensate in the
vent pipe.
H
A maximum of five 90° elbows may
be installed in
combined
length of the
exhaust vent/air intake pipe system
(excluding termination elbows, tees,
hoods and couplings).
5
2
8
5
2
6
8
v
3
.8
For solvent cement and primer:
H
H
H
H
Use only in well ventilated areas
H
H
H
H
Do not use near flame or open fire
H
H
H
H
Use only the solvent cement and
primer appropriate for the venting
material being used
H
H
H
H
Solvent cements for plastic pipe are
flammable liquids and must be kept
away from all sources of ignition
CAUTION
Ensure that the entire venting
system is protected from physical
damage. A damaged venting system
may cause unsafe conditions.
WARNING
The venting system is approved for
indoor installations only.
Do not install the venting system
outdoors.
WARNING
IMPORTANT
IMPORTANT
Summary of Contents for Vitodens 100-W WB1A-24
Page 78: ...78 5285 268 v3 8 ...
Page 79: ...79 5285 268 v3 8 ...