Single Wall Venting (Room Air Dependent)
75
Component Installation Guide
(continued)
Vent termination location requirements - vertical
The vent must be installed observing local regulations in addition to National Codes, CAN/CSA-B149.1 or 2 (for installations
in Canada) or ANSI-Z223.1 or NFPA 54 (for installations in the U.S.A.).
See table below for the following two conditions
.
H
For sloped roof applications with distance b greater than 18”/450 mm
H
For flat roof applications
Table 49.
Boiler Model
a
(min.distance)
WB1A 8-24, 8-30
18”/
450 mm
*1
WB2 6-24C, 6-24,
8-32
18”/
450 mm
*1
WB2 11-44, 15-60
18”/
450 mm
*1
*1
See WARNING below.
H
For sloped roof applications with distance b less than 18”/450 mm
a minimum 18”/450 mm
b <18”/450 mm
A vent used in a special venting
system with positive vent pressure and
passing through a roof shall extend at
least 18”/450 mm above the highest
point where it passes through the roof
and any other obstruction within a
horizontal distance of 18”/450 mm.
The special vent system shall not be
routed into, through, or within any
other vent such as an existing masonry
or factory-built chimney.
A masonry chimney flue may be used
to route the venting system only if no
other appliance is vented in the same
flue.
Single-wall vent termination installation
Install the vent termination coupling,
along with the bird screen, for sloped
or flat roof collars in accordance with
the manufacturer’s instructions.
5
2
8
5
2
6
8
v
3
.8
Fig. 65
a
b
Fig. 66
a
Vent termination must be at least
12”/300 mm above the anticipated
snow level (consult your local building
authorities or local weather office).
Locate vent termination in such a way
that it cannot be blocked by snow.
WARNING
Fig. 67
a
b
IMPORTANT