44
5600 332 v1.3
Vitodens 100-W, WB1B Installation & Service
Installation Examples
(continued)
Connections
Model WB1B
26
35
∆
t
Output Btu/h
83,000
108,000
30° F rise (GPM)
5.5
---
35° F rise (GPM)
4.7
6.2
40° F rise (GPM)
4.2
5.4
Maximum Flow Rates
Vitodens 100-W, WB1B 26, 35 with one heating circuit
and the CombiPLUS
Legend
AV Air vent
PRV Pressure relief valve (boiler)
PRV* Pressure relief valve (DHW 150 psi)
WSE Water softner equipment
A
Vitodens 100-W
B
Room thermostat
C
Heating circuit
D
CombiPLUS
E
Expansion tank
Note:
The use of a low-loss header is recommended if the
water flow rate is less than 1.7 GPM (400 L/h) or
more than 6.2 GPM (1400 L/h).
The low-loss header is available as accessory part.
Built-in pump residual head for the heating system
side is 6.0 ft. of water column at the boiler
maximum flow rate of 6.2 GPM.
Note:
Heating circuit C in the examples should be
designed to 30º F to 40º F (16.7º C to 22.2º C).
For lesser delta T design, system layout designer
must use one of the examples (5 or 6) on the
following pages.