77
5600 332 v1.3
Vitodens 100-W, WB1B Installation & Service
Troubleshooting
Boiler Connection
Start-up and Maintenance
Remove front panel
Check boiler temperature sensor
1.
Loosen the screws at the bottom of the boiler; do not
remove completely.
2.
Remove the front panel.
Resistance in K
Ω
Boiler water temperature
1.
Disconnect cables from boiler temperature sensor
A
.
2.
Measure resistance of the boiler temperature sensor
and compare with resistance/boiler water temperature
curve shown.
3.
If the value measured differs significantly, replace the
sensor.
WARNING
The boiler temperature sensor is immersed in the
heating water (risk of scalding).
Drain the boiler before replacing the sensor.