Vitodens 100-W, WB1B Installation & Service
Technical Data
Additional Information
Call for heat priority logic table
Priority
Control operating mode
Required signal
*
1
Pump output
Pump off delay
1
Freeze protection
Boiler temperature < 41º F (5º C)
On
4 minutes (240 seconds)
2
OpenTherm
OT signal
On
20 seconds
3
CombiPLUS
DHW flow sensor / temp. sensor
On
none
4
DHW / external heat
demand
Close DHW contact in power / pump
module
- boiler set-point temp. = 78º C
(non-adjustable)
On
20 seconds
5
Outdoor temperature
sensor*
2
- Temperature dial “
tr
” setting
- RT contact closed or OT
connection terminals 1 & 2 shorted.
On
4 minutes (240 seconds)
6
Room thermostat
(RT terminal)
Close RT contact in power / pump
module.
On
4 minutes (240 seconds)
The Vitodens 100-W, WB1B boiler has several operating control options. The following table provides the priority levels
of each of the different operating controllers.
*
1
Boiler control will adjust the boiler water temperature set-point to the highest of all input signals.
*
2
Priority #6 (outdoor temperature sensor / RT contact) not functional when OT inputs are recognized by the boiler control.