Vitodens 200-W B2HA 112, 150 Service
39
5683 710 - 09
Outdoor Reset Programming Unit
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
(e.g. HK1B mixing valve
control)
(e.g. HK3B
*1
multiple
mixing valve control)
*1
LON communication
module
Participant no. 1
Code “77:1”
Participant no. 10
Code “77:10”
Participant no. 11
Set code “77:11”
Participant no. 99
Control unit is fault
manager
Code “79:1”
Control unit is not fault
manager
Code “79:0”
Control unit is not fault
manager
Code “79:0”
Device is fault manager
Control unit transmits the
time
Code “7B:1”
The control unit receives
the time
Set code “81:3”
The control unit receives
the time
Set code “81:3”
Device receives the time
Control unit transmits
outside temperature
Set code “97:2”
Control unit receives
outside temperature
Set code “97:1”
Control unit receives
outside temperature
Set code “97:1”
--
LON participant fault
monitoring
Code “9C:20”
LON participant fault
monitoring
Code “9C:20”
LON participant fault
monitoring
Code “9C:20”
--
Connecting the Boiler Control to a LON System
(continued)
The LON communication module (accessory) must be
connected.
Note:
The data transfer via the LON can take several
minutes.
Single boiler system with Vitotronic 200-H, HK1B and
Vitotronic 200-H, HK3B mixing valve controls and
Vitocom LON communication module
Set the LON participant numbers and other functions
via coding level 2 (see table below)
Note:
In the same LON system, the same participant
number cannot be allocated twice. Only one
Vitotronic may be programmed as fault manager.
*1 Refer to the separate Installation Instructions of accessories.
Refer to the Installation Instructions for
the LON communication module