Vitodens 200-W B2HA 112, 150 Service
49
5683 710 - 09
General
(continued)
Coding 2
Value address
00: ...
System type
Description
7
4
One heating circuit with mixing valve M2 (heating circuit 2) and one
heating circuit with mixing valve M3 (heating circuit 3), without DHW heating.
8
4
One heating circuit with mixing valve M2 (heating circuit 2) and one
heating circuit with mixing valve M3 (heating circuit 3), with DHW heating.
9
5
One heating circuit without mixing valve A1 (heating circuit 1),
one heating circuit with mixing valve M2 (heating circuit 2) and
one heating circuit with mixing valve M3 (heating circuit 3),
without DHW heating (code is adjusted automatically).
10
5
One heating circuit without mixing valve A1 (heating circuit 1),
one heating circuit with mixing valve M2 (heating circuit 2) and
one heating circuit with mixing valve M3 (heating circuit 3),
with DHW heating (code is adjusted automatically).
Coding in the factory setting
Possible change
11:
≠
9
No access to the coding
addresses for the combustion
controller parameters
11:9
Access open to the coding
addresses for the combustion
controller parameters.
2A:0
Without wireless outside
temperature sensor
2A:1
With wireless outside
temperature sensor (automatic
recognition).
2A:2
Wireless outside temperature
sensor not used.
2D:0
DO NOT ADJUST
--
--
32:0
Without extension AM1
32:1
With extension AM1 (automatic
recognition).
33:1
Function output A1 at
extension AM1: Heating
circuit pump
33:0
Function output A1: DHW
recirculation pump.
33:2
Function output A1: Circulation
pump for DHW tank heating.
34:0
Function output A2 at
extension AM1: DHW
recirculation pump
34:1
Function output A2: Heating
circuit pump.
34:2
Function output A2: Circulation
pump for DHW tank heating.
35:0
Without extension EA1
35:1
With extension EA1 (automatic
recognition).
36:0
Function, output
aBJ
at
extension EA1: Fault message
36:1
Function output
aBJ
: Feed pump.
36:2
Function output
aBJ
: DHW
recirculation pump.