Vitodens 200-W B2HA 112, 150 Service
5683 710 - 09
76
Fault Codes
(continued)
Troubleshooting
*1
Control mode: Boiler/burner fully operational (fault code must be verified and reset).
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked: If fault cause is corrected, burner resumes operation.
*2
Detailed fault code coding address 38:xx (if available).
Fault code
on display
Detailed fault
Code
*2
System behavior
*1
Cause
Corrective action
D8
-
Control mode
Input DE3 reports a
fault at extension EA1
Remove fault at appliance
concerned.
DA
-
Control mode without
room influence
Short circuit on room
temperature sensor,
heating circuit 1 without
mixing valve
Check the room temperature
sensor, heating circuit 1
without mixing valve.
DB
-
Control mode without
room influence
Room temperature
sensor, shorted out
heating circuit 2 with
mixing valve
Check the room temperature
sensor, heating circuit 2.
DC
-
Control mode without
room influence
Short circuit, room
temperature sensor,
heating circuit 3 (with
mixing valve)
Check room temperature
sensor, heating circuit 3
DD
-
Control mode without
room influence
Room temperature
sensor cable broken,
heating circuit 1
without mixing valve
Check the room temperature
sensor, heating circuit 1 and
the remote control setting
(see page 81).
DE
Control mode without
room influence
Room temperature
sensor cable broken,
heating circuit 2 with
mixing valve
Check the room temperature
sensor, heating circuit 2 and
the remote control settings
(see page 81).
DF
-
Control mode without
room influence
Room temperature
sensor cable broken,
heating circuit 3
(with mixing valve)
Check room temperature
sensor for heating circuit 3
and remote control settings
(see page 81).
E0
-
Control mode
Fault external LON
participant
Check connections and LON
participants.
E1
202
Burner in a fault mode
Ionization current too
high during calibration
Check gap between ionization
electrode and burner gauze
assembly (see page 23). In open
flue mode, prevent very dusty
conditions for the combustion air.
Press reset button
R
.
E2
NOT USED
201
Burner in a fault mode
Heating water flow
rate too low during
calibration.
Ensure adequate circulation
volume. Check boiler pump flow.
Remove scaling, blockage.
Press reset button
R
.
E3
204
Burner in a fault mode
Heat transfer too low
during calibration.
Temperature limiter
caused shutdown.
Ensure adequate heat transfer.
Press reset button
R
.