Vitodens 200-W B2HA 112, 150 Service
83
5683 710 - 09
Troubleshooting
Corrective Action
(continued)
Heating circuit
Rotary selector S1 setting
Heating circuit with mixing
valve M2 (heating circuit 2) 2
Heating circuit with mixing
valve M3 (heating circuit 3) 4
Extension kit for heating circuit with mixing valve
Checking the setting of rotary selector S1:
The rotary selector on the PCB of the extension kit
defines the assignment to the relevant heating circuit.
Note:
The rotational direction of the mixing valve motor
during its self-test. Then set the mixing valve
manually to “Open”.
Note:
The flow temperature sensor must now capture
a higher temperature. If the temperature drops,
either the motor is turning in the wrong direction
or the mixing valve set is incorrectly fitted.
Checking the rotational direction of the mixing valve motor
After being switched on, the boiler implements a self-test.
During this, the mixing valve is opened and closed again.
Changing the rotational direction of the mixing valve motor
(if required)
1. Remove the upper casing cover of the extension kit.
2. At plug
gS
, switch the cores at terminals“
|
” and “
~
”.
3. Refit the casing cover.
WARNING
Electric shock hazard indicates an
imminently hazardous situation which,
if not avoided, may result in loss of life,
serious injury or substantial product /
property damage. Before opening the
boiler, disconnect main power.
Checking the Vitotronic 200-H (accessories)
The Vitotronic 200-H is connected to the control unit via
the LON. To test the connection, carry out a participant
check at the boiler control unit (see page 38).