77
Coding in the delivered condition
Possible change
Pump control in "standby mode"
F7:25
In "Standby mode", the
circulation pump in the
heating circuit connection
set is constantly on (only
for constant temperature
control units)
F7:0
In "Standby mode", the cir-
culation pump in the heat-
ing circuit connection set is
constantly off
F7:1
to
F7:24
In "Standby mode", the cir-
culation pump in the heat-
ing circuit connection set is
started 1 to 24 times per
day for 10 min each time.
Start temperature raising
F8:-5
Temperature limit for ter-
minating reduced mode
-5 °C, see example on
page 157.
Observe the setting of
coding address "A3". (on-
ly for weather-compensa-
ted control units)
F8:+10
to
F8:-60
Temperature limit adjusta-
ble from
+10 to -60 °C
F8:-61
Function disabled
End temperature raising
F9:-14
Temperature limit for rais-
ing the reduced set room
temperature -14 ºC, see
example on page 157.
(only for weather-com-
pensated control units)
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
Set flow temperature increase
FA:20
Raising the set boiler wa-
ter or flow temperature by
20 % when changing
from operation with re-
duced room temperature
to operation with stand-
ard room temperature.
See example on
page 158 (only for
weather-compensated
control units).
FA:0
to
FA:50
Temperature rise adjusta-
ble from 0 to 50 %
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5585 174 GB
Service