86
Coding in the delivered condition
Possible change
54:2
With Vitosolic 200 (auto-
matic recognition)
54:4
With solar control module
SM1 with auxiliary function,
e.g. central heating backup
(automatic recognition)
6E:50
No measured outside
temperature correction
6E:0
to
6E:100
Outside temperature cor-
rection in 0.1 K steps.
0 to 49 = -5 K to -0.1 K
51 to 100 = 0.1 K to 5 K
76:0
Without communication
module
76:1
With LON communication
module (automatic recog-
nition). Only for weather-
compensated control
units.
76:2
With cascade communica-
tion module (automatic rec-
ognition). Only for constant
temperature control units.
77:1
LON subscriber number
(only for weather-com-
pensated control units)
77:2
to
77:99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note
Allocate each number on-
ly once.
79:1
With LON communication
module: control unit is
fault manager (only for
weather-compensated
control units).
79:0
Control unit is not fault
manager
7b:1
With LON communication
module: control unit
transmits the time (only
for weather-compensa-
ted control units).
7b:0
Does not transmit time
Code 2
General/group "1"
(cont.)