■ Setting range: 35 to 60 °C
■ Connection: G 1 male thread
Thermostatic DHW circulation set
For integration in hot water systems
with
DHW circulation pipe
Part no. ZK01284
■ Automatic thermostatic mixing valve
■ Setting range: 35 to 60 °C
■ Integral non-return valves
■ Connection: R ¾ male thread
■ Thermal insulation
Solar pressure gauge
For installation in surface mounted and flush mounted connection
sets
Part no. 7459103
■ Display range: 0 to 10 bar
■ With tees for installation in the connection sets
Connection bend for condensate drain
Part no. 7461025
Connection line from the appliance: DN 20
Drain connection: DN 40
Neutralising system with wall mounting bracket
Part no. ZK03652
With neutralising granulate
200
300
361
61
61
131
Neutralising granulate
Part no. ZK03654
2.5 kg
To match the neutralising system, part no. ZK03652
Condensate lifting system
Part no. ZK02486
Automatic condensate removal pump for condensate with a pH
value of ≥ 2.8 from gas condensing boilers
Components:
■ Condensate container 2.0 l
■ Centrifugal pump
■ Non-return valve
■ Connecting cable (1.5 m long) for fault messages
■ Power cable (1.5 m long) with plug
■ 4 connection apertures
7
30 mm for condensate drain with con-
nector
7
max. 40 mm)
■ Drain hose
7
10 mm (5 m long)
85
171
1500
279
84
108
204
262
A
130
B
A
Condensate drain
B
4 x condensate inlet (closed in delivered condition)
Specification
Rated voltage
230 V~
Rated frequency
50 Hz
Power consumption
70 W
IP rating
IP 20
Installation accessories
(cont.)
84
VIESMANN
VITODENS
7
5853906
Summary of Contents for Vitodens 200-W B2HE