106
Coding in the delivered condition
Possible change
d5:0
With external heating pro-
gram changeover (ob-
serve setting for coding
addresses "3A", "3b" and
"3C" in group
"Gener-
al"
).
Heating program
switches to "Constant
central heating with re-
duced room tempera-
ture" or "Standby mode"
(subject to the settings of
the set reduced room
temperature) (only for
weather-compensated
control units).
d5:1
The heating program
changes to "Constant op-
eration with standard room
temperature".
d6:0
Heating circuit pump
stays in control mode at
signal "External block-
ing"
d6:1
Heating circuit pump stops
at signal "External block-
ing" (subject to coding ad-
dresses "3A", "3b" and
"3C")
d6:2
Heating circuit pump starts
at signal "External block-
ing" (subject to coding ad-
dresses "3A", "3b" and
"3C")
d7:0
Heating circuit pump
stays in control mode at
signal "External de-
mand"
d7:1
Heating circuit pump stops
at signal "External de-
mand" (subject to coding
addresses "3A", "3b" and
"3C")
d7:2
Heating circuit pump starts
at signal "External de-
mand" (subject to coding
addresses "3A", "3b" and
"3C")
d8:0
With extension EA1:
No heating program
changeover.
d8:1
Heating program change-
over via input DE1.
d8:2
Heating program change-
over via input DE2.
Code 2
"Heating circuit ..."/group 5
(cont.)
5773 216 GB
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...