132
Dis-
played
fault
code
Const.
Weath.-
comp.
System char-
acteristics
Cause
Measures
EA
X
X
Burner in a fault
state
Ionisation
current out-
side permissi-
ble range dur-
ing calibration
(deviation
from previous
level too
great)
Check flue system;
remedy flue gas re-
circulation if re-
quired.
In open flue opera-
tion, prevent high
incidence of dust in
the combustion
air.
Press reset button
R
Following several
unsuccessful reset
attempts, replace
boiler coding card
and press reset
button
R
Eb
X
X
Burner in a fault
state
Repeated
flame loss
during cali-
bration
Check gap be-
tween ionisation
electrode and
burner gauze as-
sembly (see
page 52).
Check allocation of
gas type (see
page 52).
Check flue system;
remedy flue gas re-
circulation if re-
quired.
Press reset button
R
EC
X
X
Burner in a fault
state
Parameter
fault during
calibration
Press reset button
R
or
Replace boiler cod-
ing card and press
reset button
R
Ed
X
X
Burner in a fault
state
Internal fault
Replace control
unit
Troubleshooting
Fault codes
(cont.)
5773 216 GB
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...