80
Coding in the delivered condition
Possible change
Lock out controls
8F:0
Operation in the standard
menu and extended
menu enabled
Note
The respective code is
only activated when you
exit the service menu
(see page 111).
8F:1
Operation in standard
menu
and
extended menu
blocked.
Emissions test mode can
be enabled
8F:2
Operation enabled in the
standard menu and
blocked in the extended
menu.
Emissions test mode can
be enabled
Set flow temperature for external demand
9b:70
Set flow temperature for
external demand 70 °C
9b:0
to
9b:127
Set value adjustable from 0
to 127 °C (limited by boiler-
specific parameters)
"Boiler"/group 2
Select
"Boiler"
for weather-compensa-
ted control units (see page 77).
Select
"2"
for constant temperature con-
trol units (see page 77).
Coding
Coding in the delivered condition
Possible change
Single/multi-boiler system
01:1
Do not adjust (only for
constant temperature
control units)
Burner service in 100 hours
21:0
No service interval (hours
run) selected
21:1
to
21:100
The number of hours run
before the burner should
be serviced is adjustable
from 100 to 10 000 h.
One adjusting step
≙
100 h
Code 1
"General"/group 1
(cont.)
5773 216 GB
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...