82
Coding
Coding in the delivered condition
Possible change
Economy function outside temperature
A5:5
With heating circuit pump
logic function (economy
control): heating circuit
pump "OFF" when the
outside temperature (AT)
is 1 K higher than the set
room temperature (RT
set
)
AT > RT
set
+ 1 K (only for
weather-compensated
control units)
A5:0
Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF"; see fol-
lowing table
Parameter address
A5:...
With heating circuit pump logic function: Heating cir-
cuit pump "OFF"
1
AT > RT
set
+ 5 K
2
AT > RT
set
+ 4 K
3
AT > RT
set
+ 3 K
4
AT > RT
set
+ 2 K
5
AT > RT
set
+ 1 K
6
AT > RT
set
7
to
AT > RT
set
– 1 K
15
AT > RT
set
– 9 K
Code 1
"Heating circuit ..."/group 5
(cont.)
5773 216 GB