85
Coding in the delivered condition
Possible change
Min. flow temperature heating circuit
C5:20
Electronic minimum flow
temperature limit 20 °C
(only in operation with
standard room tempera-
ture; only for weather-
compensated control
units)
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 °C (limited by
boiler-specific parameters)
Max. flow temperature heating circuit
C6:74
Electronic maximum flow
temperature limit 74 °C
(only for weather-com-
pensated control units)
C6:10
to
C6:127
Maximum limit adjustable
from 10 to 127 °C (limited
by boiler-specific parame-
ters)
Heating program - changeover
d5:0
With external heating pro-
gram changeover (ob-
serve setting for coding
addresses "3A", "3b" and
"3C" in group
"Gener-
al"
).
Heating program
switches to "Constant
central heating with re-
duced room tempera-
ture" or "Standby mode"
(subject to the settings of
the set reduced room
temperature) (only for
weather-compensated
control units).
d5:1
The heating program
changes to "Constant op-
eration with standard room
temperature".
Ext. heating program changeover to heating circuit
d8:0
With extension EA1:
No heating program
changeover.
d8:1
Heating program change-
over via input DE1.
d8:2
Heating program change-
over via input DE2.
d8:3
Heating program change-
over via input DE3.
Code 1
"Heating circuit ..."/group 5
(cont.)
5773 216 GB
Service
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...