98
Coding in the delivered condition
Possible change
Pause time set permanent-
ly (specified by boiler cod-
ing card)
06:...
Maximum limit of the boil-
er water temperature, de-
faulted in °C by the boiler
coding card
06:20
to
06:127
Maximum limit adjustable
within the ranges specified
by the boiler
0d:0
Do not adjust
0E:0
Do not adjust
13:1
Do not adjust
14:1
Do not adjust
15:1
Do not adjust
21:0
No service interval (hours
run) selected.
21:1
to
21:100
The number of hours run
before the burner should
be serviced is adjustable
from 100 to 10 000 h.
One adjusting step
≙
100 h
23:0
No interval for burner
service
23:1
to
23:24
Interval adjustable from 1
to 24 months
24:0
"Service"
not shown on
display
24:1
"Service"
is shown on dis-
play (the address is auto-
matically set and must be
manually reset after a serv-
ice has been carried out)
28:0
No burner interval igni-
tion
28:1
to
28:24
Time interval adjustable
from 1 h to 24 h. The burner
is force-started for 30 s at a
time (only when operating
with LPG).
2E:0
Do not adjust
2F:0
Venting program/fill pro-
gram disabled
2F:1
Venting program enabled
2F:2
Fill program enabled
30:1
Internal variable speed
circulation pump (auto-
matic adjustment)
30:0
Internal circulation pump
without variable speed
(e.g. temporarily for serv-
ice)
Code 2
"Boiler"/group 2
(cont.)
5773 216 GB
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...