Single boiler system with Vitotronic 050 and Vitocom 300
Boiler control
unit
Vitotronic 050
Vitotronic 050
Vitocom
User no. 1
Code "77: 1"
User no. 10
Code "77: 10"
User no. 11
Set code
"77: 11"
User no. 99
Control unit is fault
manager
*
1
Code "79: 1"
Control unit is not
fault manager
*
1
Code "79: 0"
Control unit is not
fault manager
*
1
Code "79: 0"
Control unit is
fault manager
Sent time via LON
Code "7b: 1"
Time received via
LON
Set code
"81: 3"
Time received via
LON
Set code
"81: 3"
Time received
via LON
Transmit outside
temperature via
LON
Code "97: 2"
The outside tem-
perature is re-
ceived via LON
Set code
"97: 1"
The outside tem-
perature is received
via LON
Set code
"97: 1"
—
Implementing a user check (in conjunction with the LON sys-
tem)
Communication with the system devices connected to the fault manager is
tested with a user check.
Preconditions:
&
The control unit must be programmed as fault manager (code "79:1").
&
The LON user number must be programmed in all control units (see page 31).
&
The fault manager LON user list must be up to date (see page 31).
Further details regarding the individual steps
(cont.)
32
Initial start-up, inspection, maintenance
5692
569
GB
*1
In each heating system,
only one Vitotronic
may be programmed as fault manager.
Summary of Contents for Vitodens 300
Page 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Page 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Page 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Page 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Page 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Page 127: ...127 5692 569 GB...