Coding in the delivered condition
Possible change
31:65
Set speed of the inter-
nal circulation pump
when operated as boiler
circuit pump 65%, de-
faulted by the boiler
coding card
31:0
to
31:100
Set speed adjustable
from 0 to 100%. However,
the boiler coding card de-
faults a minimum speed
(e.g. when operating with
a low loss header)
32:0
Influencing signal "Ex-
ternal blocking" on cir-
culation pumps: All
pumps in control func-
tion
32:1
to
32:15
Influencing signal "Exter-
nal blocking" on circula-
tion pumps: see the
following table
Coding
Internal
circula-
tion pump
Heating cir-
cuit pump
Heating cir-
cuit without
mixer
Heating circuit
pump
Heating circuit
with mixer
Cylinder primary
pump
0
Control
funct.
Control funct. Control funct.
Control funct.
1
Control
funct.
Control funct. Control funct.
OFF
2
Control
funct.
Control funct. OFF
Control funct.
3
Control
funct.
Control funct. OFF
OFF
4
Control
funct.
OFF
Control funct.
Control funct.
5
Control
funct.
OFF
Control funct.
OFF
6
Control
funct.
OFF
OFF
Control funct.
7
Control
funct.
OFF
OFF
OFF
8
OFF
Control funct. Control funct.
Control funct.
9
OFF
Control funct. Control funct.
OFF
10
OFF
Control funct. OFF
Control funct.
11
OFF
Control funct. OFF
OFF
12
OFF
OFF
Control funct.
Control funct.
13
OFF
OFF
Control funct.
OFF
14
OFF
OFF
OFF
Control funct.
15
OFF
OFF
OFF
OFF
Code 2
(cont.)
45
Coding
5692
569
GB
Summary of Contents for Vitodens 300
Page 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Page 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Page 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Page 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Page 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Page 127: ...127 5692 569 GB...