Setting and test va-
lues
Set value
Initial
start-up
Service
Date:
By:
Static pressure
mbar
max. 57.5 mbar
Supply pressure
(flow pressure)
=
for natural gas E
mbar
17.4-25 mbar
=
for natural gas LL
mbar
17.4-25 mbar
=
for LPG
mbar
42.5-57.5 mbar
Tick gas type
Carbon dioxide con-
tent CO
2
&
at lower rated output
% vol.
&
at upper rated output
% vol.
Oxygen content O
2
&
at lower rated output
% vol.
&
at upper rated output
% vol.
Carbon monoxide
content CO
&
at lower rated output
ppm
&
at upper rated output
ppm
Ionisation current
µA
min. 4 µA
Commissioning/service reports