Wiring Diagrams
400 ºF / 204 ºC
235 ºF / 113 ºC
Legend
41
Terminals in plug
R
Relay coil 1
1R
Contact of relay 1
LC
Limit contact in boiler control
T
120 V / 24V, class II transformer
F1
Fuse (slow blow)
VD
Vent damper
ES
End switch in vent damper
FRS
Flame roll-out switch
BVS
Blocked vent switch
L1
120 V (hot)
N
120 V (neutral)
34
Vitogas 100, GS1 Ladder Diagram of Ignition System
H
Demand for heat causes vent damper
blade to open, closing vent damper
end switch ES. 120 V is available to
transformer.
H
Ignition module is energized with 24 V
from the 24 V transformer.
H
Pilot valve is energized with 24 V.
Pilot sparks and pilot gas flows. Once
pilot proves, 24 V is applied to
“MV/PV” and “MV” energizing main
valve.
H
Burner cycles on and off in response
to operating control (room thermostat,
end switch of zone valve, separate
indoor/outdoor reset control).
H
Ignition system can cycle off
adjustable high limit aquastat in boiler
control during a demand for heat.
H
BVS (blocked vent switch) or FRS
(flame roll-out switch) can de-energize
ignition system.
Vitotronic boiler controls and
Vitogas 100, GS1 Service
Instructions
5
1
6
7
4
6
3
v
1
.3