13
Example: Single boiler system with control unit Vitotronic 300, type GW2
(V300GW2); heating circuit control unit Vitotronic 200-H, type HK3 (V050HK3)
installed downstream and Vitogate 200, type EIB
Vitotronic 300
Vitotronic 200-H
Vitogate 200
LON
LON
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 98
Control unit is fault man-
ager
Code "79:1"
Control unit is not fault
manager
Code "79:0"
Device is fault manager
Viessmann system num-
ber
Code "98:1"
Viessmann system num-
ber
Code "98:1"
—
LON subscriber fault mon-
itoring
Code "9C:20"
LON subscriber fault mon-
itoring
Code "9C:20"
—
Updating LON subscriber list
Preconditions:
■ All subscribers must be connected
■ The control unit
must
be programmed
as
fault manager
(code "79:1").
Press the following keys:
1.
L
+
d
simultaneously for approx.
2 s.
The subscriber check has
been initiated.
2.
e
The subscriber list is upda-
ted after approx. 2 min.
The subscriber check is
completed.
Carrying out subscriber check
In conjunction with LON.
Commissioning
Vitotronic control unit LON integration
(cont.)
5592 880 GB
Service