6
The Vitogate 200, type EIB is suitable for
rail mounting (TS 35 to
EN 50 022 35 x 15 and 35 x 7.5) in control
panels and commercially available dis-
tribution boards.
Connection to the Vitotronic control unit
The Viessmann LON is designed for the "Line" BUS topology with a terminator at
both ends (accessories). For free wiring with a central terminator (BUS terminator),
please see the "Viessmann LON manual" at
www.viessmann.de/lon
.
The transfer distances for LON are subject to the electrical properties of the respec-
tive cabling. For this reason, only use the stated cable types. Use only
one
type of
cable within one LON.
Cable types (on site):
■ 2-core cable, CAT 5, screened
■ JY(St)Y 2 x 2 x 0.8 mm (telephone cable)
Observe the cabling requirements for the operation of the LON interface FTT 10A
(see www.echelon.com).
All Viessmann LON devices are connected via RJ45 plugs. The Viessmann LON
always requires cores "1" and "2" plus the screen. The cores are interchangeable.
The installation is therefore reverse polarity protected.
Note
When connecting appliances/devices and during wiring, observe the requirements of
protection class II, i.e. 8.0 mm air and creep path or maintain a 2.0 mm insulation
thickness against live parts.
Ensure a safe electrical separation for all on-site components (incl. PC/laptops) to
ensure conformity to EN 60 335 or IEC 65.
Installation sequence
Fitting the Vitogate 200, type EIB
5592 880 GB