47
Coding in the delivered condition
Possible change
9C:20
Monitoring LON subscrib-
ers.
If a subscriber fails to
respond, the values
specified inside the con-
trol unit will be used after
20 min. Only then will a
fault message be issued.
9C:0
No monitoring
9C:5
to
9C:60
The time is adjustable from
5 to 60 min
9F:8
Differential temperature
8 K; only in conjunction
with a mixer circuit
9F:0
to
9F:40
Differential temperature
adjustable from 0 to 40 K
Boiler circuit, mixer circuit
A0:0
Without remote control
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)
Codes
Code 2
(cont.)
5692 774 GB