54
Coding in the delivered condition
Possible change
F9:-14
Below an outside temper-
ature of -14 °C, the set
room temperature will be
raised to the value selec-
ted as set room tempera-
ture, if the system oper-
ates with the standard
room temperature, see
the example on
page 81
F9:+10
to
F9:-60
Limit for raising the set
room temperature to the
value selected for standard
mode adjustable from +10
to -60 °C
FA:20
Raising the set flow tem-
perature for the transition
from reduced room tem-
perature to standard
room temperature mode
by 20%, see the example
on page 82
FA:0
to
FA:50
Raising the set flow tem-
perature for the transition
from reduced room tem-
perature mode to standard
room temperature mode,
adjustable from 0 to 50%
Fb:30
Duration for raising the
set flow temperature (see
coding address FA):
60 min, see the example
on page 82
Fb:0
to
Fb:150
Duration for raising the set
flow temperature adjusta-
ble from 0 to 150 (corre-
sponds to 0 to 300 min)
Resetting codes to their delivered condition
Press the following keys:
1.
L
+
G
simultaneously for
approx. 2 s.
2.
e
"
Standard setting? Yes
"
appears.
3.
d
to confirm
or
4.
a
/
b
to select "
Standard set-
ting? No
".
Codes
Code 2
(cont.)
5692 774 GB