75
Checking the fuse
F1
1.
Switch OFF the power.
2.
Release the side closures and pivot
the control unit down.
3.
Remove cover
A
.
4.
Check fuse F1 (see connection and
wiring diagram).
Extension kit for heating circuit with mixer
Checking the rotational direction of
the mixer motor
1.
Switch ON/OFF switch
A
at the
extension kit first OFF and then ON
again. The device will carry out the
following self-test:
■ Mixer "Close" (150 s)
■ Pump "ON" (10 s)
■ Mixer "Open" (10 s)
■ Mixer "Close" (10 s)
Then standard control mode
resumes.
Troubleshooting
Repairs
(cont.)
5692 799 GB