background image

Power supply for accessories

The power supply of accessories can be connected directly to the
control unit. This connection is controlled with the system ON/OFF
switch (max. 4 A).
Where the boiler is installed in a wet area, the power supply con-
nection of accessories must not be carried out at the control unit.

A

Reference point Vitopend top edge

B

Area for electrical supply cables

Allow all cables/leads to protrude approx. 1300 mm from the wall
in area

B

.

Cables
NYM-J
3 × 1.5 mm

2

2-core min.
0.75 mm

2

NYM-O 3 x 1.5 mm

2

Power supply
cables (also for
accessories)

Fault notification

External exten-
sion H1 and H2
(KM BUS)

Outside tempera-
ture sensor

Vitotronic 050
(LON)

Extension kit for
heating circuit with
mixer (KM BUS)

Vitotrol 100, type -
UTD

Vitotrol 200

Vitotrol 300

Vitotrol 100, type -
UTA

Interlocking circuit

Install an interlock for open flue operation if required, if an extrac-
tor (e.g. cooker hood) is fitted in the room providing the boiler air
supply.
For this, the internal extension H2 (accessories) can be used.
This switches the extractors OFF when the burner is started.

Accessories for Vitopend installation

Installation template for finished walls

Part no. 7186 957

&

Wall mounting fixture

&

Installation brace

&

Mounting panel with shut-off valves and boiler fill & drain valve

&

Pipe bends Ø 15/22

&

Gas stop cock G ¾"

Part no. 7186 958

&

Wall mounting fixture

&

Installation brace

&

Mounting panel with shut-off valves and boiler fill & drain valve

&

Pipe bends Ø 16/22

&

Gas stop cock G ¾"

Part no. 7186 959

&

Wall mounting fixture

&

Installation brace

&

Mounting panel with shut-off valves and boiler fill & drain valve

&

Pipe bends Ø 16/20

&

Gas stop cock G ¾"

5822

335-1

G

B

VITOPEND 222

VIESMANN

13

Pre-installation

(cont.)

Summary of Contents for VITOPEND 100 WH0A

Page 1: ...r for balanced flue operation Control unit for constant temperature or weather compen sated operation is included in the equipment price For natural gas and LPG VIESMANN Datasheet Part numbers and prices see pricelist VITOPEND 222 Gas fired boiler with an integral primary cylinder for open or balanced flue operation 10 5 to 24 30 kW File in Vitotec folder register 5 5822 335 1 GB 3 2006 ...

Page 2: ...d easily accessible AquaBloc hydraulic unit Multi connect system All components including the heat exchanger are accessible from the front side clearances are no longer required A Stainless steel primary cylinder B Diaphragm expansion vessel C Modulating burner D Aqua Block E Vitotronic control unit Selection Vitopend 222 Type WHSA Vitopend 100 Type WHEA Vitopend 200 Type WHKA Vitopend 100 Type WH...

Page 3: ...Vitopend 222 Type WHSA Vitopend 100 Type WHEA Vitopend 200 Type WHKA Vitopend 100 Type WH0A Simultaneous operation 5822 335 1 GB VITOPEND 222 VIESMANN 3 Selection cont ...

Page 4: ...W primary cylinder Capacity l 50 50 Permissible operating pressure bar 10 10 Minimum pressure cold water connection bar 0 5 0 5 Continuous DHW output kW 30 30 for DHW heating from 10 to 40 C l h 860 860 Performance factor NL 2 0 2 0 Max DHW draw off rate at the given DHW performance factor NL and DHW heating from 10 to 40 C max 10 min l min 20 20 Connection values Relative to the max load Gas HuB ...

Page 5: ...the gas supply pressure is higher than the maximum permitted value install a separate gas governor upstream of the system Balanced flue operation A Area for electrical supply cables E Drain GA Gas connection HR Heating return HV Heating flow KW Cold water WW DHW Note For dimensions of on site pipe connections see from page 10 5822 335 1 GB VITOPEND 222 VIESMANN 5 Specification Vitopend 222 cont ...

Page 6: ...coaxial 60 100 80 125 mm 136 c Flue outlet bend 90 coaxial 60 100 mm 95 Boiler flue connection and boiler flue connection bend 90 parallel 80 80 mm 228 Boiler flue connection and boiler flue connection bend 90 coaxial 60 100 80 125 mm 246 Installation location parallel adaptor 5822 335 1 GB 6 VIESMANN VITOPEND 222 Specification Vitopend 222 cont ...

Page 7: ...onnections see from page 10 Dimensions a External Ø mm 100 b Boiler flue connection coaxial 60 100 mm 70 Boiler flue connection coaxial 60 100 80 125 mm 136 c Flue outlet bend 90 coaxial 60 100 mm 95 Boiler flue connection and boiler flue connection bend 90 coaxial 60 100 80 125 mm 246 5822 335 1 GB VITOPEND 222 VIESMANN 7 Specification Vitopend 222 cont ...

Page 8: ...cal connections E Drain GA Gas connection HR Heating return HV Heating flow KW Cold water WW DHW Note For dimensions of on site pipe connections see from page 10 5822 335 1 GB 8 VIESMANN VITOPEND 222 Specification Vitopend 222 cont ...

Page 9: ...stallation Clearance for maintenance work Maintain a clearance of 700 mm in front of the Vitopend for main tenance work Maintenance clearances to the l h or r h side of the Vitopend are not required 5822 335 1 GB VITOPEND 222 VIESMANN 9 Specification Vitopend 222 cont ...

Page 10: ...ed walls A Installation template B Vitopend position C Area for electrical supply cables Allow all cables leads to protrude approx 1300 mm from the wall E Drain GA Gas connection G HR Heating return G HV Heating flow G KW Cold water G SIV Connection options for safety valve secondary side WW Hot water G Note For on site connection dimensions for pipes see page 13 5822 335 1 GB 10 VIESMANN VITOPEND...

Page 11: ...ables leads to protrude approx 1300 mm from the wall E Drain GA Gas connection G HR Heating return G HV Heating flow G KW Cold water G SIV Connection options for safety valve secondary side WW Hot water G Note For on site connection dimensions for pipes see page 14 5822 335 1 GB VITOPEND 222 VIESMANN 11 Pre installation cont ...

Page 12: ...connection R HR Heating return R HV Heating flow R KW Cold water R SIV Connection options for safety valve secondary side WW Hot water R Electrical connection Power supply Ensure the power supply connections comply with the require ments of your local electricity supply company and current VDE or local regulations Protect the power supply cable with a fuse with a maximum rating of 16 A Provide the...

Page 13: ...trol 200 Vitotrol 300 Vitotrol 100 type UTA Interlocking circuit Install an interlock for open flue operation if required if an extrac tor e g cooker hood is fitted in the room providing the boiler air supply For this the internal extension H2 accessories can be used This switches the extractors OFF when the burner is started Accessories for Vitopend installation Installation template for finished...

Page 14: ...off valves and boiler fill drain valve Pipe bends Ø 15 22 Gas angle valve G Part no 7186 962 Mounting panel with shut off valves and boiler fill drain valve Pipe bends Ø 16 20 Gas angle valve G Part no 7186 963 Mounting panel with shut off valves and boiler fill drain valve Pipe bends Ø 16 22 Gas angle valve G Fitting cover Part no 7192 890 Filling facility with shut off device Part no 7189 502 58...

Page 15: ... Vitotronic 100 type HC1 constant temperature mode Structure and functions Modular design The control unit is integrated into the boiler The control unit comprises a basic unit electronic modules and a programming unit Basic unit ON OFF switch Optolink laptop interface Operating and fault display Reset button Fuses Programming unit Display Adjustment and display of temperatures and codes 5822 335 ...

Page 16: ...t temperature during operation 0 to 90 C during storage and transport 20 to 70 C Outlet temperature sensor The outlet temperature sensor is integrated into the boiler Specification Protection IP 32 Permissible ambient temperature during operation 0 to 90 C during storage and transport 20 to 70 C Internal extension H1 The internal extension H1 is integrated into the control unit Function Switches t...

Page 17: ...or 230 V Connection via a LV cable is possible in conjunction with the external extension H4 accessories Specification Rated voltage 3 V Rated breaking capacity of the zero volt contact max 6 1 A 230 V min 1 mA 5 V Protection IP 20 to EN 60529 safeguard through appropri ate design and installation Function RS type 1B to EN 60730 1 Permissible ambient temperature during operation 0 to 50 C during s...

Page 18: ...sumption 2 5 VA Protection class I Protection IP 41 Permissible ambient temperature during operation 0 to 40 C Installation in living spaces or boiler rooms standard ambient conditions during storage and transport 20 to 65 C Vitotronic 200 type HO1 weather compensated mode Structure and functions Layout and functions Modular construction The control unit is integrated into the boiler The control u...

Page 19: ... Adjusting the heating curves slope and level The Vitotronic 200 controls the boiler water temperature flow temperature of the heating circuit without mixer and the flow tem perature of the heating circuit with mixer in conjunction with the extension kit for one heating circuit with mixer subject to outside temperature The boiler water temperature is automatically boosted by between 0 and 40 K hig...

Page 20: ...t with mixer Notes regarding the Vitotrol 200 and 300 If required the Vitotrol 200 and 300 can also be used together in a single heating system respectively for one heating circuit each Vitotrol 200 Part no 7450 017 KM BUS user The Vitotrol 200 remote control regulates the heating program for one heating circuit and the required set room temperature in stan dard mode from any room in the house The...

Page 21: ... perature as well as a rapid heat up at the start of the heating operation if suitably encoded Connection 2 core lead length max 50 m even if connecting several remote control units Never route this lead immediately next to 230 400 V cables LV plug as standard delivery Specification Power supply via KM BUS Power consumption 0 5 W Protection class III Protection IP 30 to EN 60529 safeguard through ...

Page 22: ...or PC Fault messages are transmitted to the following communica tion services via the telephone system Fax D1 D2 mobile phone Standard delivery Vitocom 100 Power supply cable 2 0 m long Connecting cable with RJ11 plug for telephone socket 3 0 m long Adaptor RJ11 TAE6N KM BUS cable with plug aVG 3 0 m long For accessories and further details see the Viessmann technical guide Communication systems O...

Page 23: ... the basic module for dimensions or 7143 431 10 digital inputs 7 analog inputs 2 may be configured as pulsed inputs 2 digital outputs 1 M BUS interface with connection of up to for example 250 M BUS capable heat meters with M BUS slave interface to EN 1434 3 see the basic module for dimensions 7159 767 Uninterruptible power supply unit 1 UPS 7143 432 Additional rechargeable battery pack 1 for UPS ...

Page 24: ... motor is mounted directly onto the Viessmann mixer DN 20 to 50 and R to 1 Mixer electronics with mixer motor Specification Rated voltage 230 V Rated frequency 50 Hz Power consumption 6 5 W Protection IP 32D to EN 60529 safeguard through appropri ate design and installation Protection class I Permissible ambient temperature during operation 0 to 40 C during storage and transport 20 to 65 C Rated b...

Page 25: ...ensor Secured with a tie Specification Protection IP 32 to EN 60529 safeguard through appropri ate design and installation Permissible ambient temperature during operation 0 to 120 C during storage and transport 20 to 70 C Immersion thermostat Part no 7151 728 May be used as a maximum temperature limiter for underfloor heating systems The temperature limiter is installed into the heating flow and ...

Page 26: ...ature Specification Lead length 3 75 m fully wired Protection IP 32 to EN 60529 safeguard through appro priate design and installa tion Permissible ambient temperature during operation 0 to 90 C during storage and transport 20 to 70 C LON communication module Part no 7179 113 For connection of one Vitotronic 050 heating circuit control unit or the Vitocom 300 comprising one PCB KM BUS distributor ...

Page 27: ...a a 0 10 V input Only with the Vitotronic 200 type HO1 External heating program changeover Specification Rated voltage 230 V Rated frequency 50 Hz Rated current 4 A Power consumption 4 W Protection class I Protection IP 32 Permissible ambient temperature during operation 0 to 40 C Installation in living spaces or boiler rooms standard ambient condi tions during storage and transport 20 to 65 C Ext...

Page 28: ...e directly routed through the roof The installation location must be safe from the risk of frost The maximum ambient temperature of the system should not exceed 45 C Provide a drain in the boiler room for the blow off line of the safety valve and if required for the condensate trap of the balanced flue system Electrical interlocks for extractors extractor hoods etc are not required with balanced f...

Page 29: ...ing devices with extraction to the outside cooker hoods extractors etc ensure that air extraction will not create negative pressure inside the installation room Otherwise flue gases could return into the room if the extraction equipment and Vitopend are operated simultaneously In such cases install an interlocking circuit For this the internal exten sion H2 is available Operating Vitopend in wet a...

Page 30: ...r this Underfloor heating circuit Install a temperature limiter into the flow of the underfloor heating circuit to limit the maximum temperature Observe DIN 18560 2 The underfloor heating circuit should be connected via a mixer For this see the Vitoset technical guide chapter Control of under floor heating systems Low loss header We recommend the use of a low loss header for systems with a water c...

Page 31: ...for use in conjunction with zinc pla ted galvanised pipes Sizing the diaphragm expansion vessel for heating water A diaphragm expansion vessel is integrated into the Vitopend Inlet pressure 0 75 bar Blow off pressure 3 0 bar Terminal pressure 2 5 bar Capacity 8 litres Vitopend content 1 2 litres When making the water connections check that the size of the expansion vessel matches the system condit...

Page 32: ...esponds to that of the ceiling e g B30 It was verified as part of the DIN DVGW type test that nowhere on Vitopend or the balanced flue system will surface tempera tures higher than 40 K above room temperature occur Minimum clearances to combustible materials inside the instal lation location or in connection with the roof outlet do not have to be observed The vertical roof outlet has been tested a...

Page 33: ...lue condensate trap Ø 60 100 mm Part no 7197 769 Drain outlet kit Part no 7179 307 External wall terminal type C12x coaxial system size Ø 60 100 mm Install an inspection aperture for checking and cleaning the flue pipe in the balanced flue system Route the connection piece with a gradient of at least 3º The external wall terminal and horizontal roof outlet have been tested and _ certified as a con...

Page 34: ... no 7194 833 Balanced flue condensate trap Ø 60 100 mm Part no 7194 846 Drain outlet kit Part no 7179 307 Vertical pitched and flat roof outlet parallel system size Ø 80 80 mm For installing the Vitopend in an attic type C32x The roof outlet may only be used where the ceiling of the occu pied room also forms part of the roof or only the roof structure is located above the ceiling pitched attic Whe...

Page 35: ...o Ø 80 80 mm colour black Part no 7338 656 colour terracotta Part no 7183 940 3 Roof tile colour black Part no 7338 644 colour terracotta Part no 7183 692 or Flat roof collar Part no 7338 645 4 Universal dummy covers Part no 7185 140 5 Fixing clamp Ø 125 mm Part no 7198 596 Bend Ø 80 mm 90 Part no 7198 578 45 2 pieces Part no 7198 579 6 Pipe Ø 80 mm 1 m long trim to size Part no 7198 580 0 5 m lon...

Page 36: ...o 7179 307 External wall terminal type C12 parallel system size Ø 80 80 mm Route the connection piece with a gradient of at least 3º The external wall terminal and the horizontal roof outlet have been tested and _ certified as a concentric balanced flue sys tem as one technical unit with the Vitopend Thermally insulate the air supply pipe in unheated rooms From a pipe length of 2 5 m upwards insta...

Page 37: ...rt of the DIN DVGW type test that nowhere on Vitopend or the balanced flue system will surface tempera tures higher than 40 K above room temperature occur Minimum clearances to combustible materials inside the instal lation location or in connection with the roof outlet do not have to be observed The vertical roof outlet has been tested and _ certified as a concentric balanced flue system as one t...

Page 38: ...art no 7198 591 Drain outlet kit Part no 7179 307 External wall terminal and horizontal roof outlet type C12x coaxial system size Ø 80 125 mm Install an inspection aperture for checking and cleaning the flue pipe in the balanced flue system Route the connection piece with a gradient of at least 3º The external wall terminal and horizontal roof outlet have been tested and _ certified as a concentri...

Page 39: ...outlet kit Part no 7179 307 Horizontal roof outlet A Ventilation air B Flue gas 1 Boiler flue connection coaxial with integral condensate trap Ø 80 125 mm must be ordered separately Part no 7198 586 2 Balanced flue bend 87 1 piece Part no 7198 594 45 2 pieces Part no 7198 593 3 Balanced flue inspection piece straight Ø 80 125 mm Part no 7198 598 4 Balanced flue pipe 1 m long trim to size Part no 7...

Page 40: ...be connected with the shortest possible pipe to the chimney stack on the same floor as where it is installed The chimney cross section must be at least the same as the Vitopend flue outlet The chimney cross section must be calculated in accordance with EN 13384 Take the following measures if the calculation results in an awareness that the actual temperature will constantly fall below the dew poin...

Page 41: ... 2 75 cm2 unobstructed cross section The combustion air apertures may be able to be closed if safety equipment can ensure that the burner can only be operated if the aperture is open Tested quality CE designation according to current EC Directives 5822 335 1 GB VITOPEND 222 VIESMANN 41 Flue gas system accessories for open flue operation aluminium cont ...

Page 42: ...ww viessmann com Subject to technical modifications Viessmann Limited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com 5822 335 1 GB Printed on environmentally friendly chlorine free bleached paper 42 VIESMANN VITOPEND 222 ...

Reviews: