10.3 Vitosolic 200, type SD4, part no. Z007 388
Specification
Construction
The control unit comprises:
■ PCB
■ LCD
■ Selector keys
■ Terminals:
– Sensors
– Solar cell
– Pumps
– Pulse counter input for connection of flow meters
– KM BUS
– Central fault message facility
– V BUS for large display
– Power supply (on-site ON/OFF switch)
■ PWM outputs for controlling the solar circuit pumps
■ Relay for actuating the pumps and valves
■ Available languages:
– German
– Bulgarian
– Czech
– Danish
– English
– Spanish
– Estonian
– French
– Croatian
– Italian
– Latvian
– Lithuanian
– Hungarian
– Dutch (Flemish)
– Polish
– Russian
– Romanian
– Slovenian
– Finnish
– Serbian
– Swedish
– Turkish
– Slovakian
The standard delivery includes collector temperature sensor, cylinder
temperature sensor and temperature sensor (swimming pool water/
heating water buffer cylinder).
Collector temperature sensor
For connection inside the appliance.
On-site extension of the connecting lead:
■ 2-core lead, length up to 60 m with a cross-section of 1.5 mm
2
(cop-
per)
■ Never route this lead immediately next to 230/400 V cables
Cable length
2.5 m
IP rating
IP 32 to EN 60529, ensure
through design/installation
Sensor type
Viessmann NTC 20 kΩ at
25 °C
Permissible ambient temperature
– During operation
−20 to +200 °C
– During storage and transport
−20 to +70 °C
Cylinder temperature sensor or temperature sensor (swimming
pool water/heating water buffer cylinder)
For connection inside the appliance.
On-site extension of the connecting lead:
■ 2-core lead, length up to 60 m with a cross-section of 1.5 mm
2
(cop-
per)
■ Never route this lead immediately next to 230/400 V cables
Cable length
3.75 m
IP rating
IP 32 to EN 60529, ensure
through design/installation
Sensor type
Viessmann NTC 10 kΩ at
25 °C
Permissible ambient temperature
– During operation
0 to +90 °C
– During storage and transport
−20 to +70 °C
For systems with Viessmann DHW cylinders, the cylinder temperature
sensor is installed in the threaded elbow (see chapter "Specification"
of the relevant DHW cylinder and chapter "Installation accessories")
in the heating water return.
When a temperature sensor (swimming pool) is used to record the
swimming pool water temperature, the stainless steel sensor well
(accessories) can be installed directly into the swimming pool return.
Functions
■ Switching the solar circuit pumps for DHW and/or swimming pool
heating or other consumers
■ Electronic limiter for the temperature in the DHW cylinder (safety
shutdown at 90 °C)
■ Collector safety shutdown
■ DHW
and
swimming pool heating:
DHW heating can be set as a priority. When the swimming pool water
is heated (consumer with the lower set temperature), the circulation
pump will be switched OFF in accordance with a timer, to establish
whether the DHW cylinder (consumer with the higher set tempera-
ture) can be reheated. The system continues to heat the swimming
pool water, if the DHW cylinder is being heated or if the temperature
of the heat transfer medium is insufficient to heat it up.
■ DHW heating
and
central heating with a heating water buffer cylin-
der:
The buffer cylinder water is heated by solar energy. The DHW water
is heated by the buffer cylinder water. When the temperature inside
the heating water buffer cylinder exceeds the heating return tem-
perature by the set value, a 3-way valve is actuated and the heating
return water is routed via the heating water buffer cylinder to the
boiler to raise the return temperature.
For further functions, see chapter "Functions".
Specification
250
47
204
Rated voltage
230 V ~
Rated frequency
50 Hz
Rated current
6 A
Power consumption
6 W
(in standby mode 0.9 W)
Safety category
II
IP rating
IP 20 to EN 60529, ensure
through design/installation
Mode of operation
Type 1B to EN 60730-1
Solar control units
(cont.)
40
VIESMANN
VITOSOL
10