Installation on Sloped Roofs
(Vertical Tube Orientation)
16
Overview of System Installation
This installation method is best suited
for DHW or pool systems with constant
loads.
This method is not recommended for
applications that combine DHW and
space heating supplement or any other
application where long periods of
stagnation are expected.
Horizontal tube orientation is
recommended for applications that
combine DHW and space heating
supplement (see page 8).
If this installation method is used for
applications that combine DHW and
space heating supplement, a heat
rejection circuit must be used to avoid
collector stagnation.
The collectors should be installed so
that the header is slightly inclined
upwards towards the supply and return
pipe connections, where an air vent
should be located.