Additional information
22
Specification
Rated output
kW
15
18
22
27
33
40
50
63
Type of burner
VEK
I1
VEK
I1
VEK
I1
VEK
I1
VEK
I1
VEK
I2
VEK
II1
VEK
II2
Type test no.
acc. to DINEN267
5G971/2001S
5G972/2001S
Voltage
V
230
Frequency
Hz
50
Motor speed
rpm
2
800
Version
single stage
Oil pump
output
Litres/h
45
Connections
Suction and return
line on oil hoses
R (female thread)
e
"
line on oil hoses
(part of standard
delivery).
Standard values for burner settings
Please note:
Check whether service instructions are valid for boiler concerned (see notes on applicability, page2 and serial no. on
burner type plate).
Rated output
kW
15
18
22
27
33
40
50
63
Oil burner nozzle
Make
Fluidics
*
1
Make
Danfoss
Type
Gph
Type
Gph
60
º
SF
0.40
60
º
SF/
60
º
HF
0.45/0.50
60
º
HF
0.60
/
45
º
SF
0.75
60
º
SR
0.85
45
º
SF
1.00
60
º
S
1.25
80
º
H
1.50
Oil pressure approx.
*
2
bar
9.0
9.0
9.0
8.5
9.0
10.0
11.5
10.5
Oil flow rate
kg/h
Litres/h
1.40
1.65
1.68
1.98
2.06
2.42
2.53
2.97
3.09
3.63
3.74
4.40
4.68
5.50
5.89
6.93
Air damper setting
Position of air damper
see page 7
7.5
8.0
8.5
10.0
13.5
16.5
17.0
25.0
Blast tube connection
setting
Position of setscrew
see page 7
mm
3.0
3.0
5.0
8.0
10.0
8.0
10.0
14.0
Static burner pressure
*
3
mbar
Position of test nipple
see page 7
3.23.6
3.23.6
3.23.6
3.03.3
2.53.0
2.53.0
3.23.7
2.53.0
Aluminium deflector
of sensor plate
No. of plugs remaining
in deflector
0
0
0
2
0
0
0
0
*1
The requirements laid down for the certificate of environmental excellence were verified only with the nozzles shown.
*2
Due to nozzle tolerances and varying oil characteristics, the oil pressure may vary from that indicated by the values shown.
*3
To check the burner settings.
5692452
GB