18
Serial no.
7537 157
7537 158
7537 159
Transferable heating output
at
75 °C heating water flow temperature/
35 °C heating water return temperature and
10 °C cold water inlet temperature/
60 °C DHW outlet temperature
kW
up to 80
up to 120
up to 240
Content
Heating water
l
1.7
2.3
4.0
DHW
l
1.7
2.3
4.0
Connections
(DIN 2999)
Heating water flow and return
R
1
1
1
¼
Cold water, DHW
R
1
1
1
¼
Weight
kg
25
27
60
Permiss. operating pressure
Heating water and DHW sides
bar
MPa
10
1
10
1
10
1
Power consumption per pump
On the primary/secondary side
■
Min.
W
3
3
8
■
Max.
W
45
45
130
Max. heating water temperature
With mixer assembly (for modulating operation)
°C
110
110
110
Without mixer assembly (for constant operation)
°C
75
75
75
Specification
Specification
5549 892 GB