24
Possible settings
Display
Description
Factory setting
Setting range
"Pasteurisatn"
Enables the pasteurisation function
"No"
(disabled)
■
"No"
(disabled)
■
"Yes"
(enabled)
"Man. start"
To start the function manually, see
page 24
—
■
"Start"
■
"Cancel"
"T pasteu. set"
Set DHW temperature for pasteurisation
60 °C
60 to 75 °C
"Pasteu. dur."
Duration of pasteurisation
60 min
30 to 240 min
"Pasteu.day"
Selection of days for automatic pasteurisa-
tion start
—
—
"Pasteu. time"
Time for automatic pasteurisation start
01:00 h
00:00 to 23:59 h
Selecting the set DHW temperature
Press the following keys:
1.
for
"DHW circ."
.
2.
OK
to confirm.
3.
for
"Pasteurisatn"
.
4.
OK
to confirm.
5.
for
"T pasteu. set"
.
6.
OK
to confirm.
7.
/
for selecting the set DHW temperature.
8.
2 x OK to confirm.
Setting the duration of pasteurisation
Note
In a cascade, the duration set here is split in equal
parts among the individual appliances.
Press the following keys:
1.
for
"DHW circ."
.
2.
OK
to confirm.
3.
for
"Pasteurisatn"
.
4.
OK
to confirm.
5.
for
"Pasteu. dur."
.
6.
OK
to confirm.
7.
/
for setting the duration of pasteurisation.
8.
2 x OK to confirm.
Starting pasteurisation manually
Press the following keys:
1.
for
"DHW circ."
.
2.
OK to confirm.
3.
for
"Pasteurisatn"
.
4.
OK to confirm.
5.
OK to confirm
"Man. start Start"
.
Pasteurisation ends when the
"Pasteu. dur."
has expired or can be terminated manually
(see next chapter).
Commissioning
Setting pasteurisation
(cont.)