Additional information
121
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Address:
Value
Possible change
2C: 5
General
Maximum run-on time of boiler isolation
valve 5 minutes
2C: 0
No run-on time
2C: 5
General
Maximum run-on time of boiler isolation
valve 5 minutes
2C: 1
to
2C: 60
Run-on time adjustable
from 1 to 60 minutes
2d: 0
Boiler
Shunt pump ON only when requested
2d: 1
Shunt pump ON continuously
40:125
General
Operating time of actuating drive, boiler
isolation valve, 3-port mixing valve or
mixing valve motor in conjunction with
return temperature raising facility
125 seconds
40: 5
to
40:199
Operating time adjustable
from 5 to 199 seconds
4A: 0
General
Plug
aJ
A
not installed
4A: 1
Plug
aJ
A
installed
(e.g. temperature sensor of
Therm-Control);
automatically recognized
4b: 0
General
Plug
aJ
B
not installed
4b: 1
Plug
aJ
B
installed
(e.g. temperature sensor T2);
automatically recognized
4C: 2
General
Connections at plug
sÖ
A1:
Therm-Control switch contact
4C: 1
Primary pump of DHW heating
4C: 2
General
Connections at plug
sÖ
A1:
Therm-Control switch contact
4C: 3
Circulation pump of flue gas/water
heat exchanger
4d: 1
General
Connections at plug
sL
:
Shunt pump
4d: 2
Boiler circuit pump
4d: 1
General
Connections at plug
sL
:
Shunt pump
4d: 3
Boiler circuit pump with boiler
isolation valve function
4E: 0
General
Connections at plug
gS
:
Boiler isolation valve or 3-port mixing
valve for return temperature raising facility
4E: 1
3-port valve of DHW heating
4F: 5
General
Shunt pump, boiler circuit pump or
distributor pump with 5 minutes run-on
4F: 0
No pump run-on
4F: 5
General
Shunt pump, boiler circuit pump or
distributor pump with 5 minutes run-on
time
4F: 1
to
4F: 60
Run-on time adjustable
from 1 to 60 minutes
54: 0
General
Without solar control unit
54: 1
With Vitosolic 100;
will be recognised automatically
54: 2
With Vitosolic 200;
will be recognised automatically
5
3
5
1
3
3
8
v