Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Address:
Value
Possible change
62: 10
DHW
Circulation pump with run-on time of
10 minutes
62: 0
Circulation pump without run-on
time
10 minutes
62: 1
to
62: 15
Run-on time variable from 1 to 15
minutes
67: 40
DHW
With Vitosolic:
3rd DHW set-point 40
˚
C/ 104
˚
F
67: 0
Without 3rd DHW set-point
3rd DHW set-point 40
˚
C/ 104
˚
F
Reloading suppression will be active
above set temperature. DHW tank is
heated only by solar heating system.
67: 1
to
67: 95
Input of a 3
rd
set DHW set-point
temperature; adjustable
from 1 to 95
˚
C / 34 to 203
˚
F
63: 0
DHW
Without additional function for
domestic hot water heating
63: 15
Twice per day
63: 0
DHW
Without additional function for
domestic hot water heating
63: 1
Additional function: Once per day
63: 0
DHW
Without additional function for
domestic hot water heating
63: 2
to
63: 14
Every 2 days
to
Every 14 days
68: 8
DHW
In conjunction with 2 tank
temperature sensors with the DHW
heating:
Switch-off point of tank heating at
setpoint value x 0.8
68: 2
to
68: 10
Factor adjustable from 0.2 to 1
per 1 increment = 0.1
69: 7
DHW
In conjunction with 2 tank
temperature sensors with the DHW
heating:
Switch-on point of tank heating at
setpoint value x 0.7
69: 1
to
69: 9
Factor adjustable from 0.1 to 0.9
per 1 increment = 0.1
76: 0
General
Without LON communication module
76: 1
With LON communication module;
recognized immediately
76: 2
With Viessmann 2-wire BUS
communication module; recognized
immediately
77: 1
General
LON participant number
77: 2
to
77: 99
LON participant number selectable
from 1 to 99
Please note:
Each number may be assigned
once
only
.
78: 1
General
LON communication released
78: 0
LON communication blocked
79: 0
General
Control unit is not error manager
79: 1
Control unit is error manager
80: 1
General
With 5 seconds time delay for fault
message
80: 0
Without time delay
80: 1
General
With 5 seconds time delay for fault
message
80: 2
to
80:199
Time delay adjustable between
10 and 995 seconds;
1 increment = 5 seconds
5
3
5
1
3
3
8