62
Coding
Code 2
(cont.)
Coding in the factory default setting
Possible change
Mixing valve circuit
(cont.)
b6: 0
With remote control unit and for the heating circuit,
operation with room temperature hook-up must be
encoded:
Without boost heating/rapid setback
b6: 1
With boost heating/rapid setback
(see page 31)
b7: 0
With remote control unit and for the heating circuit,
operation with room temperature hook-up must be
encoded:
Without start-up time optimisation
b7: 1
With start-up time optimisation (max. offset 2 h
30 min)
b7: 2
With start-up time optimisation (max. offset 15 h
50 min)
b8: 10
With remote control unit and for the heating circuit,
heating with room temperature hook-up must be
encoded:
Heat-up gradient
Start-up time optimisation
10 min/K
b8: 11
to
b8:255
Heat-up gradient start-up time optimisation
adjustable from
11 to 255 min/K
b9: 0
With remote control unit and for the heating circuit,
heating with room temperature hook-up must be
encoded:
Without learning start-up time optimisation
b9: 1
With learning start-up time optimisation
5581
529
v1.0
08/2006