16
■
The Viessmann CAN bus is designed for "line" bus
topology with a terminator at both ends (accesso-
ries).
■
With CAN bus, the transmission quality and the
cable lengths depend on the electrical properties of
the cable:
–
Only use cable types listed in the following table.
–
Only use
one
cable type within a CAN bus.
Recommended cable type (on site):
CAN bus cable
In line with ISO 11898-2, twisted pair cable, shielded
■
Cable cross-section
0.34 to 0.6 mm
2
■
Characteristic impedance
95 to 140
Ω
■
Max. length
200 m
Alternative cable types (on site):
CAN bus cable
2-core, CAT5, shielded
■
Max. length
50 m
CAN bus cable
2-core, CAT7, shielded
■
Max. length
200 m
Installation sequence
Establishing the CAN bus connection
6175460
Installation