14
Gasifying boilers VIGAS
VIGAS 18 DPA, VIGAS 26 DPA
Choose one option
+60
To start discharge fan for 60 s (used during heating-up)
ON
Switch on
⌧
Cancel display driver
Fuel „PELLETS“ Confirm to switch to pellets „
“.
▲
Change of indicated figure
Select „+60“ new graphic driver will appear. Running time of discharge
fan can be viewed in the upper corner.
+60
You can add extra 60s , maximum 360s
ON
Switch on
0
Discharge fan switched off
Fuel „WOOD“, Confirm to switch to wood „
“.
▲
Change of indicated figure
5.2 VIGAS BOILER CONTROL
with discharge fan
Fuel - WOOD
5.2.1 Boiler switch on
5.2.2 Boiler active – heating phase „ON“
5.2.3 Boiler active – burning phase „82,5°C“
Discharge fan is optional accessory for VIGAS boiler. Discharge fan assembly provides increased comfort
during heating-up and refilling mode. It helps to reduce smoke from boiler room area. When lighting up the
boiler it will help to create fire base quickly. See chap. 13.3.
When boiler in „OFF“ mode (see display), by short pressing of middle
button „ENTER“ graphic driver can be recalled.
In the heating phase, the boiler gas exhaust temperature is lower then the
minimum set-up exhaust gas temperature. Minimum and maximum
temperatures can be modified in boiler set-up parameters. Minimum
standard exhaust gas set-up temperature is up 90°C and maximum set-
up temperature is 220°C. Boiler can be in heating mode for up to 60
minutes with minimum of 2min. If boiler does not reach burning phase in
this time, it will automatically shut down – sign „END“.
The burning phase is active, when the exhaust gas temperature is
(
end) +10 °C or after reaching desired temp. Burning phase is
controlled by PID regulator on the basis of chimney and boiler temp. If the
temperature rises 1°C above desired temp., the output will be 0%. If it
decreases >2°C below desired temp., the output will start again.
By pressing choose fuel pellets „
“ or fuel wood „
“.
Warning:
Before pressing „ENTER“ it is necessary to heat-up the boiler, follow
chapter 11.4.