TSGR-21 GAS Release Panel User Manual
Vighnaharta Technologies Pvt. Ltd. Page
20
of
43
Maintenance Mode it gets visualized using LED for it. This mode is used to test smoke detector and NAC /RAC is
not get activated.
Maintenance mode Procedure
•
First panel is set as Maintenance Mode.
•
Then give smoke to the sensor.
•
The sensor will detect smoke and LCD will display show fire to the particular zone.
•
In this way multiple sensors in a single loop can be tested.
Note
: Repeat Maintenance Mode after every 3 months.
2.4.2 Servicing
Following are the servicing check list of TSGR-21 panel. Maintenance / servicing is required twice a year for each
panel.
Sr.
No.
Check point or maintenance point
OK/Not
OK
Remark
1
Before Maintenance / Servicing please evacuate / clear all
the premises
2
Clean each smoke detector using soft cloth.
3
Check panel operation on battery backup mode (mains
OFF).
4
Check panel operation on mains supply (Battery
disconnected).
5
Check all connection of panel.
6
Check Smoke Detector.
7
Check NAC output.
8
Check battery supply.
9
Check panel mounting screw.
Note
: Please send above servicing report after every 6 months.
2.4.3 Periodic inspection and test of system
For additional information on control panel faults, regular checking of the functionality of the control panel and fire
detection system by a person responsible for fire prevention in the company must ensure the availability of the fire
detection system.
Weekly Testing By The User
▪
Ensure that all indicators are showing correctly.
▪
Check that the internal buzzer are operating correctly.
▪
LCD Display shows messages from the system.