Each week, choose different manual check points so that the manual check points in the building
are tested in rotation over a prolonged period.
▪
Check all detectors and ensure that none are obstructed in any way. Enter results of tests into the
log book.
Quarterly Test
Perform Walk Test / Supervisory Test to check the healthy condition of all zones. After every 3-4
months Walk test must be carried out.
Annual Test
Additionally, test all detectors, check points and check for correct operation.
Every 2 - 3 Years
Clean smoke detectors to ensure correct operation and freedom from false alarms. Special equipment
is required for cleaning smoke detectors.
Every 4 years
Replace sealed lead acid batteries. If the operating temperature exceeds 25
o
C continuously, then the
battery may need to be replaced sooner.
Pre Check list for call:
▪
Check mains supply of system. It should not exceed 230VAC.
▪
Check supply voltage of panel. It should not be more than 27.5VDC.
▪
Check panel operation on battery backup mode.
▪
Check all Indicators are showing results as per action are taking place in the Panel. Mainly check out for the
system ON indicator is glowing.
▪
LCD display shows messages, buzzer operates.
▪
Check all the cables are connected in proper manner.
▪
Smoke detectors can detect the smoke.
▪
Check the premises evacuated / cleared to avoid accidents.